External (key-switch operated):
Reset/resound/test zone lamps evacuateSilence alarm soundersSilence fault soundersInternal:
One man detector testZone isolateRevert to short-circuit: fire (no resistors in call points)External indicators:
Sounder faultBattery/power supply faultMains onZone fireZone faultInternal indicators:
Open circuit zone faultShort circuit zone faultZone isolatedEngineer test selectedOutputs:
Two sounder circuits (alarm relay contacts can be obtained by connecting a relay to a sounder circuit)Ancillary connections for expansion modules will allow the following:
Repeater panelsMultiple sounder outputsConnection to landlord panelSpecifications
| 
 | 2 (0.8A SUPPLY) | 4 / 6 (1.5A SUPPLY) | 8/10/12/14/16/18 (4.0A SUPPLY) | 
| POWER SPECIFICATION | |||
| MAINS SUPPLY VOLTAGE | 230V±10%Va.c.50/60Hz | 230V±10%Va.c.50/60Hz | 230V±10%Va.c.50/60Hz | 
| INTERNAL POWER SUPPLY | 27 Vd.c. | 27 Vd.c. | 27 Vd.c. | 
| TOTAL OUTPUT CURRENT LIMITED TO | 800mA@240VAC | 1500mA@240VAC | 4000mA@240VAC | 
| AUXILIARY POWER OUTPUT | 27 Vd.c. | 27 Vd.c. | 27 Vd.c. | 
| MAINS SUPPLY MONITORED FOR FAILURE | YES | YES | YES | 
| BATTERY CHARGER MONITORED FOR FAILURE | YES | YES | YES | 
| BATTERIES MONITORED FOR DISCONNECTION AND FAILURE | YES | YES | YES | 
| DETECTOR CIRCUIT SPECIFICATION | |||
| NUMBER OF CIRCUITS | 2 | 4 or 6 | 8, 10, 12, 14,16,or 18 | 
| LINE FAULT MONITORED FOR OPEN CIRCUIT | YES | YES | YES | 
| LINE FAULT MONITORED FOR SHORT CIRCUIT | YES (Can be disabled) | YES (Can be disabled) | YES (Can be disabled) | 
| LINE FAULT MONITORED FOR DETECTOR REMOVAL | Yes, if End of Line Monitor Unit fitted in place of End of Line Resistor | ||
| END OF LINE RESISTOR (SUPPLIED) VALUE | 6800,5% tolerance,0.25W | 6800,5% tolerance,0.25W | 6800,5% tolerance,0.25W | 
| DETECTOR CONTINUITY DIODES | Silicon 1N4001 or Schottky type(required if End of Line Monitor Unit fitted to give Detector Removal Fault) | ||
| CALL POINT RESISTOR VALUE (NOT SUPPLIED) | 470 to 680, 0.5W | 470 to 680, 0.5W | 470 to 680, 0.5W | 
| MAXIMUM NUMBER OF SMOKE DETECTORS PER ZONE | 20(maximum detector current = 2mA) | 20(maximum detector current = 2mA) | 20(maximum detector current = 2mA) | 
| MAXIMUM NUMBER OF MANUAL CALL POINTS PER ZONE | No limit | No limit | No limit | 
| SOUNDER CIRCUIT SPECIFICATION | |||
| NUMBER OF CIRCUITS | 2 | 2 | 2 | 
| END OF LINE RESISTOR VALUE | 6800, 5%tolerance,0.25W | 6800, 5%tolerance,0.25W | 6800, 5%tolerance,0.25W | 
| LINE FAULT MONITORED FOR OPEN CIRCUIT | YES | YES | YES | 
| LINE FAULT MONITORED FOR SHORT CIRCUIT | YES | YES | YES | 
| OUTPUTS FUSED AT | 1 Amp | 1 Amp | 1.6 Amp | 
| MAXIMUM TOTAL OUTPUT CURRENT ALL OUTPUTS | 800mA | 1500mA | 4000mA | 
| MAXIMUM NO OF BELLS @ 25 mA EACH BELL | 32 | 56 | 120 | 
| MAXIMUM NO OF ELECTRONIC SOUNDERS @ 20 mA | 40 | 70 | 150 | 
| AUXILIARY RELAY CONTACTS (DO NOT CONNECT MAINS VOLTAGES) | 1A 30 Vd.c. max Voltage Free | 1A 31 Vd.c. max Voltage Free | 1A 32 Vd.c. max Voltage Free | 
| FUSES-ALL FUSES COMPLIANT TO IEC (EN60127 PT2) | |||
| MAINS TERMINAL BLOCK | 200mA T 20 mm | 400mA T 20mm | 630mA T 20mm | 
| SOUNDER OUTPUTS | 1A F 20mm | 1A F 20mm | 1.6A F 20mm | 
| AUXILIARY OUTPUT | 1A F 20mm | 1A F 20mm | 1A F 20mm | 
| BATTERY FUSE | 1.6A F 20mm | 1.6A F 20mm | 3A F 20mm | 
| DOOR RETAINING MAGNETS | DO NOT USE PANEL POWER SUPPLY AS YOU WILL DRASTICALLY REDUCE BATTERY STAND-BY TIME | ||
| CONNECTION BLOCK | |||
| LARGEST ACCEPTABLE CONDUCTOR SIZE | 2.5mm2 | 2.5mm2 | 2.5mm2 | 
| SMALLEST ACCEPTABLE CONDUCTOR SIZE | 0.75mm2 | 0.75mm2 | 0.75mm2 | 
| DIMENSIONS | |||
| ENCLOSURE(WIDTH x HEIGHT x DEPTH) | 415 x 265 x 100mm | 415 x 265 x 100mm | 415 x 265 x 100mm | 
| WEIGHT(WITHOUT BATTERIES) | 5100g | 5200g | 5500g |